City of Portland, Maine Inspections Divison Inspection Results Date Range from 6/1/2013 through 8/28/2013 Date CBL 06/03/2013 042 A007001 042 A007001 54 YORK ST 06/21/2013 042 A007001 042 A007001 042 A007001 042 A007001 042 A007001 042 A007001 042 A007001 54 YORK ST Close-in Plumbing/Framing CC Cancel/ 201245504 Building 201301154 Plumbing not reday. Contractor - Dan 838-0444 Electrical Service Passed Close-in Plumbing/Framing Electrical 201245504 Building 201245504 Building 201245504 Passed Above Ceiling Inspection Building 201245504 201245504 Above Ceiling Inspection Failed GC Dan Labrie, 838-0444, was not expecting Building Inspection. Briefly reviewed job with him. Numerous violations in Fire and Smoke walls. He said that he understood what was required and the difference between fire caulking vrs fire blocking since he sells it. Building Final - Electric Failed not ready Building 201245504 Building Dan Lebre @ 838-0444 for c of o. /gg Adam Burk W/BKL & Fire 042 A007001 54 YORK ST 08/21/2013 Passed Final - Fire Dan Lebre @ 838-0444 for c of o. /gg 54 YORK ST 08/21/2013 Electrical Close-in Dan Lebre @ 838-0444 for c of o. /gg 54 YORK ST 08/12/2013 Building 2nd floor above ceiling 712-5447 Gerry 54 YORK ST 08/12/2013 201245504 2nd floor above ceiling 712-5447 Gerry AM 54 YORK ST 08/12/2013 Status Dan @ 838-0444 for close in. /gg (Brian already passed close in on 6-3-13). /gg 54 YORK ST 07/19/2013 Sch. Type Jerry @ 712-5447 for electric service, would like inspection early in the morning. /gg 54 YORK ST 07/19/2013 Appl Type Jerry @ 712-5447 for close, would like late morning if possible. /gg 54 YORK ST 06/21/2013 Appl ID Jerry @ 712-5447 for close, would like late morning if possible. /gg 54 YORK ST 06/03/2013 Business 201245504 Building Dan Lebre @ 838-0444 for c of o. /gg 042 A007001 201245504 Certificate of Occupancy/Final Failed Provide address - 54 York St. Provide above ceiling inspection. Remove ceiling tiles along rated walls and 10% in the field Provide rated doors at rated walls. If doors have been modified, relabeling is required. Provide fire stopping at rated walls Provide complete smoke barriers Provide graspable handrails See A1.3 Extend and return Provide cut sheet on separator in Classroom 101 (Fire: Storage not allowed under stairs) Provide revised plans showing as built conditions i.e. Bathroom removed at Classroom 101 Certificate of Occupancy/Final Failed Electrical - re-identify grounding wire for data rack, support wires above ceiling, grounding for fire alarm panel incorrect was installed incorrectly, no circuit breaker number listed on alarm panel Building Dan Lebre @ 838-0444 for c of o. /gg Page 1 of 2 Certificate of Occupancy/Final Failed No sprinkler or alarm test - no alarm or sprinkler company on site City of Portland, Maine Inspections Divison Inspection Results Date Range from 6/1/2013 through 8/28/2013 Date CBL 08/21/2013 042 A007001 Business Appl ID Appl Type 201245504 Building Dan Lebre @ 838-0444 for c of o. /gg 54 YORK ST Sch. Type Status Certificate of Occupancy/Final Failed Rec'd Structural engineers report regarding existing fire escape Rec'd cut sheet on ZERN Z1180 solids interceptor. Need listing. Provide Smoke and Smoke/fire dampers as needed ie Existing Stair 1 & 2, smoke partitions. Rated walls incomplete. ie rated doors, fire stopping Smoke partition incomplete at Door 123 Basement smoke partition incompleteRooms on 2nd floor that are listed as general storage - no work done to those rooms - Contractor stated the rooms willed labeled as "restricted access" and they will be locked and not allowed for storage. 08/28/2013 042 A007001 54 YORK ST 08/28/2013 08/28/2013 Building Final - Electric Building Final - Fire Dan Lebre @ 838-0444 for c of o. /gg 042 A007001 201245504 Dan Lebre @ 838-0444 for c of o. /gg 54 YORK ST 54 YORK ST 201245504 042 A007001 201245504 Building Dan Lebre @ 838-0444 for c of o. /gg Confirmed Page 2 of 2 Certificate of Occupancy/Final Passed Other Departments need to approve prior to issuance of CO